Temp. setting range
0deg.C to 500 deg.C
Temp. display range
-200deg.C to 1300deg.C
Temp. detection accuracy
±1deg.C
Power breakingcapacity
AC100V 50/60 Hz 14.5ASingle phase
Temp. setting system
Digital setting with up/down keys
Temp. display system
Digital display for sensor and set temperatures
Recovery system after detecting overheat
Manual (Turn POWER switch ON after returning to normal from overheating condition.)
Overheat temp. detection
Shutting off power of the target device/alarm with a buzzer alternately displays Er07 and the sensor detection temperature on the measured temperature display
Temp. sensor/temp. sensor protective tube
Sheath type K thermocouple/3.2 mm dia x length of 200 mm (encapsulated in a SUS316 protective tube)
Temp. sensor/temp. sensor protective tube
a-contact 250V 3A
Connecting system of target device
3P power outlet
Safety function
Internal fuse & self diagnostic function (abnormal input temperature/memory error)
Exterior/interior
Chrome free electro galvanized cupper plate, chemical proof baking finish, stainless steel plat
Accessories
Sheath type K thermocouple (soaked part: 200 mm) x 1, main unit securing clamp x 1
External dimensions(W×D×H mm)
150×210×155mm
Power Source
AC115V/AC220VSingle-phase with step down transformer